Cable Part M2502

 

Device 1
Pin Number
Device 1
Pin Name
Direction Device 2
Pin Number
Device 2
Pin Name
Description (may be empty)
6 Rx   3 TxD  Rx (RS232) and Turn Off UPS (Contact Closure)
7 Common   5 GND  Common
9 Tx   2 RxD  Tx (RS232)

 
    7,6,1 RTS,DSR,DCD  connect

 
    8,4 CTS,DTR  connect

 

 
 
 
   
2
 
         AC Failure (Contact Closure)
4
 
     
 
 Common
5
 
     
 
 Battery Low (Contact Closure)

 